Home > Products
HV ABC Cable Copper ConductorHV ABC Cable Copper Conductor
HV ABC Cable Copper ConductorHV ABC Cable Copper Conductor

HV ABC Cable Copper Conductor

Application :

Aerial bundled cable(ABC cable) are mainly used for secondary overhead lines on poles or as feedes to residential premises.

Description

Application

Aerial bundled cable(ABC cable) are mainly used for secondary overhead lines on poles or as feedes to residential premises.

Standard

AS/NZS 3599.1

Construction

Conductors

Phase conductors are stranded circular compacted aluminium alloy 1350 to H68 condition. The standard catenary is manufactured from galvanised stranded high tensile steel. For corrosive environments catenaries of aluminium clad steel are available.

Conductor Screen, Insulation and Insulation Screen

Semiconductive conductor screen, XLPE insulation and semiconductive insulation screen are triple extruded. The insulation screen is hand strippable without preheating and complies with strippability and adhesion tests given in AS/NZS 3599.1. Figures and words “1 ONE”, “2 TWO” and “3 THREE” are printed on the insulation screen to identify the three phase cores. Alternative identification means are available on request.

A water swellable textile tape is applied over the insulation screen to prevent longitudinal ingress of moisture in the event of damage to the outer sheath.

Metallic Screen

The metallic screen comprises a layer of helically applied copper wires. For short circuit protection, two types of screens, a light and a heavy duty, are available. A separator tape to prevent the penetration of sheath material between the screen wires is applied over the metallic screen. On this design of cable it should be noted that the screens of individual cores are not in direct contact

with each other and therefore the fault current level is limited.

Sheath

High density polyethylene (HDPE) is used as the standard outer sheath of each phase core. In addition to the identification on the cores, the sheaths of each phase cable are marked with phase numbers matching those of the cores. Furthermore, identification of the bundled cable comprises embossing of the words “Olex”, the year of manufacture, and the voltage on the sheath or the use of printed tapes inserted throughout the length under the sheath of a phase cable.

Parameter

For HV ABC Cable Copper conductor:

HV ABC Cable 6.35/11kV:

Physical Data

Nominal conductor area Nominal conductor diamter Average insulation thickness Nominal diameter over insulation Average insulation screen thickness Copper wire screen stranding Nominal diameter over screen Average sheath thickness Nominal diameter over sheath Galvanised steel catenary stranding Nominal overall diameter Approx. mass
mm2 mm mm mm mm no/mm mm mm mm no/mm mm kg/km
Light duty screen
35 6.9 3.4 15.1 0.8 25/0.85 19.8 1.8 24 7/2.00 54.1 1820
35 6.9 3.4 15.1 0.8 25/0.85 19.8 1.8 24 19/2.00 58.1 2130
50 8.1 3.4 16.2 0.8 25/0.85 20.9 1.8 25.2 19/2.00 60.4 2300
70 9.7 3.4 17.8 0.8 25/0.85 22.5 1.8 26.8 19/2.00 63.6 2570
95 11.4 3.4 19.5 0.8 25/0.85 24.2 1.8 28.5 19/2.00 67 2900
120 12.8 3.4 20.9 0.8 25/0.85 25.6 1.8 29.9 19/2.00 69.8 3190
150 14.2 3.4 22.3 0.8 25/0.85 27 1.8 31.5 19/2.00 73 3530
185 15.7 3.4 23.8 0.8 25/0.85 28.5 1.8 33 19/2.00 76 3890
Heavy duty screen
35 6.9 3.4 15.1 0.8 40/0.85 19.8 1.8 24 7/2.00 54.1 2050
35 6.9 3.4 15.1 0.8 40/0.85 19.8 1.8 24 19/2.00 58.1 2360
50 8.1 3.4 16.2 0.8 23/1.35 21.9 1.8 26.2 19/2.00 62.4 2820
70 9.7 3.4 17.8 0.8 32/1.35 23.5 1.8 27.8 19/2.00 65.6 3440
95 11.4 3.4 19.5 0.8 39/1.35 25.2 1.8 29.5 19/2.00 69 4030
120 12.8 3.4 20.9 0.8 39/1.35 26.6 1.8 30.9 19/2.00 71.8 4320
150 14.2 3.4 22.3 0.8 39/1.35 28 1.8 32.5 19/2.00 75 4670
185 15.7 3.4 23.8 0.8 39/1.35 29.5 1.8 34 19/2.00 78 5020

Performance Data

Nominal conductor area DC resist. at 20℃ AC resist. at 50Hz 90℃ Inductive reactance at 50Hz Three-phase voltage drop at 50Hz 90℃ Conductor to screen capacitance Continuous current rating. A Earth fault current rating for 1s Minimum bending radius(installed) mm Projected diameter for wind loading
mm2 Ω/km Ω/km Ω/km mV/A.m μF/km Still air 1m/s wind 2m/s wind kA Core Cable mm
Light duty screen
35 0.868 1.11 0.15 1.95 0.206 99 140 165 2.1 360 540 51
35 0.868 1.11 0.158 1.95 0.206 100 145 165 2.1 360 580 53
50 0.641 0.822 0.15 1.45 0.228 120 170 200 2.1 380 600 55.4
70 0.443 0.568 0.139 1.01 0.258 150 215 250 2.1 400 640 58.6
95 0.32 0.411 0.131 0.747 0.29 180 260 305 2.1 430 670 62
120 0.253 0.325 0.126 0.603 0.317 205 300 355 2.1 450 700 64.8
150 0.206 0.265 0.122 0.505 0.343 235 340 400 2.1 470 730 68
185 0.164 0.211 0.118 0.418 0.371 265 390 460 2.1 500 760 71
Heavy duty screen
35 0.868 1.11 0.15 1.95 0.206 99 140 165 3.3 360 540 51
35 0.868 1.11 0.158 1.95 0.206 100 145 165 3.3 360 580 53
50 0.641 0.822 0.152 1.45 0.228 120 175 200 4.8 390 620 57.4
70 0.443 0.568 0.14 1.01 0.258 150 215 250 6.7 420 660 60.6