Home > Products
ABC Cable--Quadruplex Service Drop WireABC Cable--Quadruplex Service Drop Wire
ABC Cable--Quadruplex Service Drop WireABC Cable--Quadruplex Service Drop Wire

ABC Cable--Quadruplex Service Drop Wire

Application :

The quadruplex ABC cable are suitable for use as drop cable from a pole-mounted transformer,to the service entrance of a structure,or as secondary distribution between poles.

Description

Application

The quadruplex ABC cable are suitable for use as drop cable from a pole-mounted transformer,to the service entrance of a structure,or as secondary distribution between poles.The cables should be limited to the voltages of 600 volts or less (phase to phase) at conductor temperatures not to exceed 75°C for polyethylene insulation conductors or 90°C for crosslinked polyethylene(XLPE) insulated conductors.

Standard

1. ASTM: B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
   B-231 Aluminum Conductors, Concentric-Lay-Stranded.
   B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
   B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.

2. ICEA S-76-474.

Construction

The phase conductors are concentrically stranded compressed 1350-H19 aluminum and insulated polyethylene or crosslinked polyethylene(XLPE), The neutral messengers are concentrically stranded AAC, ACSR, or 6201 aluminum alloy.The conductors are manufactured with ridges for phase identification(one conductor with one ridge,one conductor with two ridges ,one conductor is plain).

Parameter
Code Name Phase Conductor Bare Neutral Approx.Weight Code Name Phase Conductor Bare Neutral Approx.Weight
Size Stranding Insulation Thickness Size Stranding XLPE PE Size Stranding Insulation Thickness Size Stranding XLPE PE
AWG - mil AWG - lbs/1000ft AWG - mil AWG - lbs/1000ft
6201 Alloy Neutral Messenger AAC Neutral Messenger
Bay 6 Solid 45 6 7 145 140 Clydesdale 4 Solid 45 4 7 208 201.8
French Coach 6 7/w 45 6 7 155 144.3 Pinto 4 7/w 45 4 7 223 207.9
German Coach 4 Solid 45 4 7 214 208.3 Mustang 2 7/w 45 2 7 333 312.6
Arabian 4 7/w 45 4 7 229 214.4 Criollo 1/0 19/w 60 1/0 7 529 504.5
Belgian 2 7/w 45 2 7 344 323.1 Percheron 2/0 19/w 60 2/0 7 649 620.5
Shetland 1/0 19/w 60 1/0 7 546 521.1 Hanoverian 3/0 19/w 60 3/0 19 799 765.6
Thoroughbred 2/0 19/w 60 2/0 7 670 641.5 Oldenburg 4/0 19/w 60 4/0 19 986 946.7
Trotter 3/0 19/w 60 3/0 7 825 791.8 Lippizaner 336.4 19/w 60 336.4 19 1,546 1,519.20
Walking 4/0 19/w 60 4/0 7 1019 979.7  
ACSR Neutral Messenger
Morochuca 6 Solid 45 6 6/1 152 147.4 Grullo 2/0 19/w 60 2/0 6/1 707 678.7
Chola 6 7/w 45 6 6/1 162 151.7 Suffolk 3/0 19/w 60 3/0 6/1 872 838.9
Morgan 4 Solid 45 4 6/1 226 220 Appaloosa 4/0 19/w 60 4/0 6/1 1079 1039.2
Hackney 4 7/w 45 4 6/1 241 226.1 Bronco 336.4 19/w 60 336.4 18/1 1613 1568.2
Palomino 2 7/w 45 2 6/1 362 342.6 Gelding 336.4 19/w 60 4/0 6/1 1548 1494.3
Costena 1/0 19/w 60 1/0 6/1 575 550.6                

Note:

(1)Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

(2)Conductor temperature of 90°C for XLP, 75°C for poly; ambient temperatures of 40°C; emissivity 0.9; 2ft./sec/wind in sun.